BXM(D)59防爆配电柜 配电箱 控制箱适用范围1、爆炸性气体环境:1区、2区2、场所中危险气体或蒸气:IIA、IIB3、温度组别:T1~T64、户内、户外(防护等级IP54, 可达IP65)Applying scope1、Explosive gas atmospheres:Zone 1&22、Dangerous gasesorvapors zone: IIA、IIB3、Temperature classes:T1~T64、Indoor and outdoor (IP 54,It could be designed as IP65 according to user′s requirements)产品特点1、铸铝合金外壳,表面喷塑2、内可装C65N(H)-C、C65N(H)-D、NC100H及类似小型断路器3、具有过载、短路保护功能4、C65N(H)-C 优先适用于照明配电系统,C65N(H)-D优先适用于动力配电系统5、进出线腔、电器元件腔分别独立6、输入:3P+N+PE 输出:3P+N+PE或1P+N+PE7、可根据用户要求特制8、可钢管或电缆布线,电缆布线须配电缆夹紧密封接头 Features1、Enclosure is made of casting aluminium alloy,surface is sprayed with plastics2、Built-in small breaker such as C65N(H)-C, C65N(H)-D,NC100H etc3、With overload and short circuit protection function4、C65N(H)-C is pferable of lighting distribution system and C65N(H)-D for power distribution system5、Inlet,outlet compartment and compo
nent compartment are independent from each other6、Input:3P+N+PE , output: 3P+N+PEor1P+N+PE7、For user′s requirements, it could be specially made8、Wiring with conduitorcable,For cable, it should be fitted with explosion-protected cable sealing connector主要技术参数 Specification 型号 防爆标志 额定工作电压(V) 主回路额定工作电流(A) 支路数 支路额定工作电流(A) 使用类别 极数 进线口规格 出线口规格电缆外径 BBX□59-4N Exde II BT6 380/400220/230 4 1,3,6,10,16,25,32,40,50,63,80,100,125 AC1,AC3 3P+N+PE3P+PE1P+N+PE G40 F16~F24.5 G20 F8~F12 BX□59-6N 6 BX□59-8N 8 BX□59-10N 10 BX□59-12N 12 BX□59-4K ≤80 4 BX□59-6K ≤125 6 BX□59-8K ≤125 8 BX□59-10K ≤125 10 BX□59-12K ≤125 12